📝 Water

Catching Water Leaks Early with Minimum Night Flow (MNF) Analysis

Argus EMS · 05.10.2026 · 6 min read

Catching Water Leaks Early with Minimum Night Flow (MNF) Analysis — Argus EMS

A water leak makes no noise. A leaking underground joint, a constantly running cistern or a garden valve left open can run unnoticed for weeks and usually reveals itself only when the bill arrives. A monthly index reading tells you how much water was lost, but not when the loss started. The minimum night flow (MNF) method looks at the hours when consumption is naturally at its lowest and makes a leak visible long before the invoice.

What Is Minimum Night Flow (MNF)?

MNF is the lowest flow a meter records during the quiet hours of the night. The concept comes from the DMA (District Metered Area) approach, in which water utilities divide the network into zones measured by inlet meters. After midnight most users in a DMA are asleep, so the flow measured in those hours is the sum of legitimate night use and leakage. Once legitimate use is estimated and subtracted from MNF, the remainder is the loss indicator for that zone. The same logic applies to a building, a residential estate or a hotel: the main meter is the zone inlet meter and the sub-meters are the sub-zones.

The strength of the method comes from comparison. A single night's MNF says little on its own; the real information is whether the night baseline has risen persistently relative to the meter's own history. A developing leak persists night after night at the same or a growing level, while one-off night use disappears the following night.

Components of Night Flow: Legitimate Use or Leak?

ComponentTypical exampleHow to tell it apart
Scheduled legitimate useIrrigation, tank and booster set filling, night cleaningStarts and stops at set times; matches a schedule
Continuous legitimate useCooling tower make-up, circulation loop top-up, process waterVaries with load or season
Cistern and fixture leaksToilet cistern, dripping tap, faulty float valveLow but uninterrupted; clear at sub-meter level
Pipework leaksUnderground line, joint or riser crackLifts the night baseline permanently
Valve or tap left openForgotten garden valve, open bypassLong, uninterrupted and steady flow

The most practical way to tell them apart is to write down every legitimate night use: once irrigation timers, tank filling hours and cooling tower make-up are recorded, each peak on the night chart can be matched to a cause. A baseline flow that has no cause and repeats every night is a suspected leak.

Why Meter Resolution and Pulse Value Matter

The quality of MNF analysis depends on the meter's ability to see low flows. On a meter with pulse output, every pulse represents a fixed volume; if the pulse value is Vp and the time between two pulses is Δt, the average flow is Q = Vp / Δt. On a meter with a large pulse value, a small leak may not produce a single pulse within the logging interval, and the chart shows zero. Mechanical meters also have a starting (minimum) flow; below it the meter does not turn at all, so a dripping fixture may never be measured.

  • On lines monitored for leaks, prefer a low pulse value or an electronic (ultrasonic or electromagnetic) meter.
  • For M-Bus meters, check whether instantaneous flow can be read in addition to the index.
  • Calculate consumption from the index difference so the period total survives a missed reading.
  • Choose a reading interval that yields enough samples inside the night window.
  • Add block or zone sub-meters behind the main meter to narrow down the leak location.

Residential Estate and Hotel Scenarios

On a residential estate the main meter never truly drops to zero at night: across a large number of apartments someone is always using water. Instead of expecting absolute zero on the main meter, you track the night's own baseline and look for a persistent rise against history. Block or riser sub-meters, on the other hand, can genuinely rest at night, so uninterrupted flow there is directly suspicious. The hours of common-area irrigation and pool top-up should be clearly defined.

In a hotel the night profile is more complex. Laundry, kitchen preparation, pool and spa top-up, night cleaning and the cooling tower can all fall into the same hours, and occupancy shifts the baseline from night to night. In these facilities the main meter alone is not enough. Monitoring kitchen, laundry and landscape lines with separate sub-meters makes it possible both to separate legitimate use and to locate the leaking zone quickly.

What to Do on Site When an Alarm Arrives

  1. Check the scheduled uses (irrigation, filling, cleaning) on the night of the alarm and rule out a legitimate cause.
  2. Use sub-meter data to narrow down the suspect zone.
  3. Run a step test during the quiet night hours by closing zone valves one at a time while watching the meter; the valve that makes the flow drop points to the leaking section.
  4. Inspect cisterns, float valves and booster tanks; a dye test is a practical method for cistern leaks.
  5. Pinpoint underground leaks with an acoustic listening device.
  6. After the repair, confirm over the following nights that MNF has returned to its previous baseline.

Minimum Night Flow Analysis in Argus EMS

Argus EMS reads water meters remotely over M-Bus and Modbus and calculates consumption from the index difference. Every morning at 06:00 a night evaluation runs for each active water meter: the minimum flow in the 02:00–05:00 quiet window is compared with the baseline learned from the meter's last 21 days. The two most recent nights are excluded from learning so that a leak cannot mask its own baseline, and no alarm is raised until at least seven nights of history exist. During learning, meters fall into two groups: resting meters, whose flow drops below the noise floor in most night samples, and continuous meters such as main meters, whose flow keeps running at night.

On a resting meter, a night counts as a violation when the minimum night flow stays above the noise floor and the meter barely rests at all during the night; two consecutive nights raise a warning and three raise a CRITICAL alarm. On a continuous meter, the system calculates how many standard deviations the night minimum sits above the learned median; the default thresholds are 3σ for warning and 4σ for critical, and the threshold must be exceeded on at least two consecutive nights. A single-night spike does not raise an alarm, and an open alarm closes when the signal disappears. Resting meters are additionally checked for long uninterrupted flow within the last day of data, which points to a valve or tap left open.

Related Content

Water Leak Early Warning — Night FlowWater Consumption Monitoring and Meter ReadingResidential & Estate Energy Managementcentralised energy monitoringwired and wireless M-BusModbus energy monitoringWhat Is Harmonic Distortion (THD)?Passive vs Active Harmonic Filter Selection

FAQ

What is minimum night flow (MNF)?
MNF is the lowest flow a meter records during the quietest night hours. Because legitimate use is at its minimum then, a persistent rise in MNF relative to the meter's own history is one of the most reliable signs of a developing leak.
How is legitimate night use separated from a leak?
Uses such as irrigation, tank filling and cooling tower make-up are tied to set hours or to load and can be matched to a schedule. A baseline flow with no cause, repeating every night and traceable to a zone with sub-meters, is a suspected leak.
When does Argus EMS raise a water leak alarm?
Every morning Argus EMS compares the minimum flow of the 02:00–05:00 window with the meter's 21-day baseline. A single-night spike raises no alarm; when the threshold is exceeded on consecutive nights, a warning or CRITICAL alarm is raised depending on the meter type and duration.

Monitor Your Facility with Argus

See Argus at Your Facility

Explore the system with your own data in a demo session.